AC power quality

Power Factor Correction Calculator

Estimate the capacitive reactive-power correction needed to raise a steady load’s lagging displacement power factor.

AC power quality

Enter measured or design values

kW
PF
PF

Estimated correction

Capacitive correction estimate
42.13 kvar
Initial reactive power75 kvar
Target reactive power32.87 kvar

Displacement power factor model for a steady load.

Engineering review requiredPower-factor correction equipment requires harmonic, resonance, switching, protection, and manufacturer review. Unbalance results do not establish a universal pass/fail threshold.

About this calculator

Estimate the capacitive reactive-power correction needed to raise a steady load’s lagging displacement power factor.

This is a preliminary kvar estimate. It does not select capacitor voltage, connection, switching, fuse, or controller ratings.

Method and assumptions

For real power P and power factor PF, reactive power Q = P × tan(arccos(PF)). Required correction is initial Q minus target Q; the result is reported as a kvar magnitude.

Enter values measured or specified for the same load, system, and operating condition. These simplified calculations do not model harmonics, transient behavior, or equipment-specific acceptance limits.

FAQs

Does this result establish compliance or equipment acceptance?

No. It is a calculation or screening metric. Apply the equipment manufacturer criteria, project requirements, and locally applicable standards.

Which voltage readings should I enter?

For the voltage screen, enter all three RMS line-to-line readings measured at the same operating condition and point in the system.

Sources

Power triangle and maximum-deviation definitions as stated in the method above. Confirm manufacturer-specific criteria before applying results.