Motors and motor circuits

Three-Phase Motor Power and Torque Calculator

Estimate three-phase motor input power, shaft horsepower, and torque from matching motor-terminal measurements and nameplate data.

Motor operating data

Electrical input and shaft details

V

Enter line-to-line RMS voltage at the motor terminals.

A

Use current measured or specified for the same operating condition.

PF

Enter a decimal from 0 to 1 from matching motor data or measurement.

%

Use the efficiency for the same voltage, load, and operating condition.

rpm

Use measured speed or the motor's rated speed for the entered operating point.

Balanced three-phase estimate

Estimated shaft output

12.08 hp
Input apparent power11.64 kVA
Input real power10.01 kW
Estimated shaft output9.01 kW
Estimated shaft torque36.1 lb-ft
Operating estimate onlyThis assumes a balanced, steady, sinusoidal three-phase load using matching motor-terminal data. Do not use VFD input values or VFD output values. It does not determine motor rating, circuit sizing, overload settings, starting performance, or suitability for an application.

About this calculator

Enter line voltage, line current, power factor, motor efficiency, and shaft speed for one operating condition. The calculator estimates electrical input power and mechanical output at the shaft.

Use motor-terminal data for a balanced three-phase motor. Do not mix readings from different load conditions or use VFD input/output measurements.

Method and assumptions

Apparent input power = √3 × line voltage × line current. Real input power = apparent power × power factor. Estimated shaft output = real input power × motor efficiency. Horsepower uses the mechanical horsepower conversion. Shaft torque = horsepower × 33,000 ÷ (2π × shaft speed in rpm).

The calculation assumes balanced sinusoidal three-phase operation and uses the entered values as a matched set. It does not account for voltage or current distortion, phase imbalance, drive losses, or changing motor efficiency with load.

Interpret the result

Use the result to compare an estimated operating point with equipment documentation or measurements. It is not a motor selection, circuit sizing, or protection decision. Verify the motor and driven equipment against their data sheets and the applicable installation requirements.

FAQs

Which voltage should I enter?

Enter line-to-line RMS voltage measured or specified at the motor terminals. Use values that correspond to the same operating condition as the current, power factor, and efficiency.

Can I use readings from a VFD?

No. This calculation assumes balanced sinusoidal motor-terminal voltage and current. VFD input and output readings include drive effects that this worksheet does not model.

How is shaft torque estimated?

The calculator converts estimated shaft horsepower and the entered shaft speed to torque. Use measured speed or a matching rated speed; torque changes with speed for the same shaft power.

Does this show whether the motor is correctly sized?

No. It estimates one operating point only. It does not evaluate starting torque, load curves, service factor, thermal limits, circuit conductors, overload protection, or the motor application.

Sources

  • NIST Guide to the SI, Appendix B.9 — conversion factors for mechanical horsepower and pound-foot.
  • Use the motor manufacturer’s data for power factor, efficiency, rated speed, and operating limits.