Fire alarm notification circuits

Notification Appliance Circuit Voltage Drop Calculator

Estimate segment-by-segment voltage drop and appliance terminal voltage for a supported two-wire DC notification circuit.

DC notification circuit

Enter circuit and device data

V DC
V DC
Ω/kft

Use manufacturer resistance at expected conductor temperature.

Route segments

ft
A
ft
A
Steady-load DC estimate

End-of-line appliance voltage

Meets entered minimum 23.82 V against a 16 V minimum.
0.18 V total drop
Segment 1 device terminal23.88 V
Segment 2 device terminal23.82 V
Estimate onlyAssumes a two-wire radial circuit with each segment carrying the sum of all appliance current at and beyond that segment. Use manufacturer appliance currents and minimum voltages. This does not verify power supply capacity, circuit classification, listing, code compliance, transient response, or installation suitability.

About this calculator

Model a radial DC notification circuit as a series of route segments. Enter each segment’s one-way length and the appliance current connected at its end to estimate voltage at each appliance location.

Use matching manufacturer data for appliance current and minimum terminal voltage, and enter conductor resistance for the expected conductor temperature.

Method and assumptions

For each segment, current equals the sum of appliance currents at that segment and every downstream segment. Segment drop is current multiplied by loop resistance; loop resistance uses twice the one-way length and entered one-conductor resistance.

This model assumes a two-wire radial circuit with steady DC load. It does not model branching topology, synchronized transient behavior, power-supply regulation, or multiple circuit paths.

FAQs

What current belongs at each segment?

Enter the appliance current connected at the end of that segment. The calculation adds that value to all downstream appliance currents to determine current in each segment.

Where do I get appliance current and minimum voltage?

Use the notification appliance manufacturer data for the selected operating mode and the power supply documentation. Do not substitute nominal current or voltage values without checking the product data.

Sources

Use the listed compatibility, current draw, and minimum operating voltage from the exact notification appliance and fire alarm power supply manufacturer documentation.