AWG, kcmil and Square Millimeter Size Chart
Look up nominal AWG diameters and bare-conductor areas alongside common kcmil sizes, with a printable chart and downloadable CSV for comparison.
Last updated:
AWG diameter and area
This is a simultaneous lookup chart, not a wire-sizing result. AWG describes a nominal conductor size. A smaller ordinary gauge number represents a larger conductor; 1/0 through 4/0 continue above 1 AWG.
Diameter is the nominal round bare-wire equivalent. It is not the outside diameter of an insulated or stranded cable. Areas are nominal geometry, rounded for display, following the AWG relationship documented in NBS/NIST Copper Wire Tables.
| AWG size | Bare equivalent diameter (mm) | Bare equivalent diameter (in.) | Area (mm²) | Area (kcmil) |
|---|---|---|---|---|
| 4/0 AWG | 11.6840 | 0.46000 | 107.2193 | 211.6000 |
| 3/0 AWG | 10.4049 | 0.40964 | 85.0288 | 167.8064 |
| 2/0 AWG | 9.2658 | 0.36480 | 67.4309 | 133.0765 |
| 1/0 AWG | 8.2515 | 0.32486 | 53.4751 | 105.5345 |
| 1 AWG | 7.3481 | 0.28930 | 42.4077 | 83.6927 |
| 2 AWG | 6.5437 | 0.25763 | 33.6308 | 66.3713 |
| 3 AWG | 5.8273 | 0.22942 | 26.6705 | 52.6348 |
| 4 AWG | 5.1894 | 0.20431 | 21.1506 | 41.7413 |
| 5 AWG | 4.6213 | 0.18194 | 16.7732 | 33.1024 |
| 6 AWG | 4.1154 | 0.16202 | 13.3018 | 26.2514 |
| 7 AWG | 3.6649 | 0.14429 | 10.5488 | 20.8183 |
| 8 AWG | 3.2636 | 0.12849 | 8.3656 | 16.5097 |
| 9 AWG | 2.9064 | 0.11442 | 6.6342 | 13.0927 |
| 10 AWG | 2.5882 | 0.10190 | 5.2612 | 10.3830 |
| 11 AWG | 2.3048 | 0.09074 | 4.1723 | 8.2341 |
| 12 AWG | 2.0525 | 0.08081 | 3.3088 | 6.5299 |
| 13 AWG | 1.8278 | 0.07196 | 2.6240 | 5.1785 |
| 14 AWG | 1.6277 | 0.06408 | 2.0809 | 4.1067 |
| 15 AWG | 1.4495 | 0.05707 | 1.6502 | 3.2568 |
| 16 AWG | 1.2908 | 0.05082 | 1.3087 | 2.5827 |
| 17 AWG | 1.1495 | 0.04526 | 1.0378 | 2.0482 |
| 18 AWG | 1.0237 | 0.04030 | 0.8230 | 1.6243 |
| 19 AWG | 0.9116 | 0.03589 | 0.6527 | 1.2881 |
| 20 AWG | 0.8118 | 0.03196 | 0.5176 | 1.0215 |
| 21 AWG | 0.7229 | 0.02846 | 0.4105 | 0.8101 |
| 22 AWG | 0.6438 | 0.02535 | 0.3255 | 0.6424 |
| 23 AWG | 0.5733 | 0.02257 | 0.2582 | 0.5095 |
| 24 AWG | 0.5106 | 0.02010 | 0.2047 | 0.4040 |
| 25 AWG | 0.4547 | 0.01790 | 0.1624 | 0.3204 |
| 26 AWG | 0.4049 | 0.01594 | 0.1288 | 0.2541 |
| 27 AWG | 0.3606 | 0.01420 | 0.1021 | 0.2015 |
| 28 AWG | 0.3211 | 0.01264 | 0.0810 | 0.1598 |
| 29 AWG | 0.2859 | 0.01126 | 0.0642 | 0.1267 |
| 30 AWG | 0.2546 | 0.01003 | 0.0509 | 0.1005 |
| 31 AWG | 0.2268 | 0.00893 | 0.0404 | 0.0797 |
| 32 AWG | 0.2019 | 0.00795 | 0.0320 | 0.0632 |
| 33 AWG | 0.1798 | 0.00708 | 0.0254 | 0.0501 |
| 34 AWG | 0.1601 | 0.00630 | 0.0201 | 0.0398 |
| 35 AWG | 0.1426 | 0.00561 | 0.0160 | 0.0315 |
| 36 AWG | 0.1270 | 0.00500 | 0.0127 | 0.0250 |
| 37 AWG | 0.1131 | 0.00445 | 0.0100 | 0.0198 |
| 38 AWG | 0.1007 | 0.00397 | 0.0080 | 0.0157 |
| 39 AWG | 0.0897 | 0.00353 | 0.0063 | 0.0125 |
| 40 AWG | 0.0799 | 0.00314 | 0.0050 | 0.0099 |
kcmil area table
One kcmil is one thousand circular mils. A circular mil is the area of a circle one mil (0.001 inch) in diameter; it is not one square mil. The area conversion is approximately 0.5067075 mm² per kcmil.
| Size (kcmil) | Area (mm²) |
|---|---|
| 250 | 126.677 |
| 300 | 152.012 |
| 350 | 177.348 |
| 400 | 202.683 |
| 500 | 253.354 |
| 600 | 304.024 |
| 700 | 354.695 |
| 750 | 380.031 |
| 800 | 405.366 |
| 900 | 456.037 |
| 1000 | 506.707 |
Download the AWG and kcmil chart (CSV)
44 AWG sizes and 11 kcmil sizes with nominal area. kcmil rows intentionally have no physical cable diameter.
Use the size comparison correctly
- A numerical area conversion is not a replacement-size approval. AWG and metric products can have different standard nominal sizes, stranding, listings, and terminal suitability.
- A 12 AWG conductor’s area is about 3.31 mm². That does not turn a 2.5 mm² or 4 mm² product into the same listed conductor.
- Use the actual manufacturer outside diameter for conduit fill, bend radius, or cable routing. Bare-equivalent diameter excludes insulation and construction differences.
- Ampacity also depends on material, insulation, terminals, ambient conditions, conductor count, wiring method, and the applicable rules. This chart intentionally has no “maximum amps” column.
For a single conversion use the existing unit converter. For conductor selection conditions use the ampacity tool and read the cable-marking reference.
For a separate circuit-performance estimate, use the voltage-drop calculator with the circuit length, load, material and size required by that tool. A nominal area lookup alone does not determine voltage drop.