Timer Relay Functions and Timing Diagrams

Compare on-delay, off-delay and interval relay behavior using trigger and output timing diagrams, then check reset behavior, trigger type and timer power requirements.

Last updated:

Compare idealized timing functions

A timing function relates a defined trigger to a defined output state. Power-on, a separate signal input and signal removal are different trigger events. Read the selected product mode and contact diagram together; a dial setting alone does not identify the function.

Compare idealized timing functions
FunctionTrigger and output conceptWhat the manual must define
On-delayAfter the trigger becomes active, output waits for the set time.Whether the trigger is supply power or a signal, and how early removal resets the timer.
Off-delayOutput is active during the trigger and remains active for the set time after removal.Required sustained timer power or the specifically supported power-off-delay design.
IntervalTrigger starts an immediate output pulse of the set duration.Retriggering, early trigger removal and reset behavior.
Repeat cycle / flasherOutput alternates on and off according to the selected timing sequence.First state and whether on/off times are independently adjustable.
On-delay waits after trigger rise; off-delay holds after trigger fall; interval pulses immediately for time t.On-delayTriggerOutputtOff-delayTriggerOutputtIntervalTriggerOutputt
Idealized sustained-supply examples. High = active; t = set time. Actual reset and retrigger behavior depends on the selected product mode.

Read the timing diagram

In the idealized diagrams, high means active, low means inactive, and t marks the set interval. On-delay begins timing at the rising trigger edge. Off-delay begins timing at the falling trigger edge. Interval begins its output pulse at the rising trigger edge. The drawings assume a suitable sustained timer supply and omit reset/retrigger details.

A relay output may contain instantaneous and timed contacts on the same product. Check the actual contact designation. Do not infer a timing function or a normally closed contact action from a generic relay terminal number.

Record the chosen mode

  1. Write the exact model, supply voltage and mode selector position.
  2. Identify the trigger terminal or supply event and its normal state.
  3. Record time range, dial setting, output contact and reset time.
  4. Check power-loss response and the effect of a repeated trigger.

Use terminal markings for contact identification and control diagrams for ordinary command logic. A timer alone does not establish a machine safety function.