Fuse Classes, Markings and Holder Compatibility

Compare common North American fuse classes and read voltage, current, interrupting, and time-response markings before checking the exact fuse and holder.

Last updated:

Common class families

A fuse class identifies a standardized family with particular rating and construction requirements. It does not by itself supply every application limit or make all members of that class identical. Use the exact fuse and holder documentation.

Selected North American low-voltage fuse families
ClassRecognition contextWhat must still be checked
CCCompact rejection-type branch-circuit fuse familyVoltage, current, holder, and the particular time-response characteristic.
JA branch-circuit family with its own dimensions and performance requirementsProduct time response and the correct Class J holder.
RK1A Class R rejection familyThe manufacturer’s current-limiting and time-current data for the exact product.
RK5Another Class R rejection familyDo not assume performance identical to RK1 just because a holder arrangement appears similar.
TCompact current-limiting branch-circuit familyCorrect voltage version, dimensions, holder, and documented response.
LA large-ampere low-voltage fuse familyApplication voltage, mounting, equipment instructions, and specified rating.
GA distinct branch-circuit fuse familySpecified holder, size/rating range, and application.
H / legacy installationsAn identification requiring care with older equipmentDo not infer modern current-limiting performance or approve an upgrade without equipment review.

This is an identification table, not a replacement matrix. Specialty semiconductor, photovoltaic, medium-voltage, automotive, and other fuse systems need their own documented criteria.

Read the complete fuse marking

Ampere rating
The marked current rating, not an automatic conductor or motor protection selection.
AC / DC voltage rating
A stated voltage application. An AC marking does not establish a DC rating.
Interrupting rating
The stated capability under the documented conditions; separate from normal load current.
Time response and product series
Use the actual time-current and let-through information. A class name alone is not a complete delay specification.
Class and dimensions
Identify the correct physical and listed family. Physical fit does not settle the electrical application.

Record all these fields with the complete catalog number and manufacturer. When coordination or equipment protection matters, retain the referenced curve and the conditions used to interpret it.

Check the holder and application

  1. Read the equipment’s specified fuse requirements and the holder’s class, voltage, and current information.
  2. Identify the installed fuse and proposed replacement by full catalog number.
  3. Compare voltage application, interrupting requirements, dimensions, time response, and any equipment-specific series/coordination conditions.
  4. Resolve a missing label or conflicting requirement before replacement; do not treat an available fuse as an approved substitute.

Use the standard ampere-rating reference for its separate lookup task and the breaker marking guide for breaker-specific information. This page does not select a fuse, establish selective coordination, or determine an assembly SCCR.

Sources

Browse all reference tables, guides, and templates